GB 50260-2013 电力设施抗震设计规范(英文版)
上QQ阅读APP看本书,新人免费读10天
设备和账号都新为新人

6 Electrical Facilities

6.1 General Requirements

6.1.1 The seismic design of electrical facilities shall comply with the following requirements:

1 For electrical facilities of important electrical installations,seismic design shall be performed when the seismic precautionary intensity is 7 degree or above.

2 For electrical facilities of common electrical installations,seismic design shall be performed when the seismic precautionary intensity is 8 degree or above.

3 For electrical facilities installed on the second and above floors indoors or elevated platforms outdoors,seismic design shall be performed when the seismic precautionary intensity is 7 degree or above.

6.1.2 The electrical equipment and communication equipment shall be selected according to the seismic precautionary criterion.For electrical facilities which are located in areas of high intensity and do not meet the seismic requirements or have strict or special requirements for seismic safety and functions,seismic isolation or energy dissipation measures may be taken.