4.3 Storage and Transportation Facilities
4.3.1 Detectors shall be equipped within fire dikes for liquid tanks for LPG,class Ⅰ and class Ⅱ flammable and combustible liquids according to the following requirements:
1 When the detection point is set on the windward side of the annual minimum wind frequency of the release source,the distance between a combustible gas detection point and a release source should not exceed 15m and that between a toxic gas detection point and a release source should not exceed 2m;
2 When the detection point is set on the leeward side of the annual minimum wind frequency of the release source,the distance between a combustible gas detection point and a release source should not exceed 5m and that between a toxic gas detection point and a release source should not exceed 1m.
4.3.2 Layout of detectors for loading/unloading facilities for LPG,class Ⅰ and class Ⅱ flammable and combustible liquids shall comply with the following requirements:
1 For railway loading/unloading platform with small loading arms,a detector should be installed at every other tank space with the horizontal distance between the detector and loading/unloading port not exceeding 15m;
2 For railway loading/unloading platform with big loading arms,a detector should be installed;
3 The horizontal distance between loading/unloading ports for tank trucks and detector shall not exceed 15m.When a buffer tank is installed in the truck loading/unloading station,arrangement of detectors shall meet the provisions in clause 4.2.1 of the specification.
4.3.3 Detectors for pumps or compressors of the loading/unloading facilities shall be arranged according to the requirements in section 4.2 of the specification.
4.3.4 Detectors for liquefied hydrocarbon loading stations shall be equipped according to the following requirements:
1 For closed or semi-open cylinder-filling workshop,the distance between filling port and detector should be within the range of 5m-7.5m;
2 Inside a closed or semi-open cylinder warehouse,the arrangement of detectors shall comply with the requirements in clause 4.2.2 of the specification.Within open cylinder warehouse,detectors shall be set every 15m-30m along the perimeter of the house,one detector shall be equipped if the perimeter of the house is less than 15m;
3 The distance between the detector and the drainage port or manifold of the surge tank should be within the range of 5m-7.5m.
4.3.5 For closed or semi-open hydrogen cylinder-filling workshop,a detector shall be equipped at its highest point above the filling port in the workshop prone to gas accumulation.
4.3.6 For loading/unloading docks with potential emission of combustible gas,a detector shall be installed within 15m of the horizontal plane of the transfer loading/unload arm.
4.3.7 For storage and transportation facilities storing and transporting toxic gas and liquid,detectors shall be equipped according to the section 4.2 and clause 3.0.10 of the specification.